How to Fuse your Solar System

By Stephen Clifton

Technical Representative

When hooking up your Renogy system,
the best way to add protection is by using fuses or circuit breakers. Fuses and
circuit breakers are used to protect the wiring from getting too hot and also
protect all devices connected in the system from catching fire or getting
damaged if a short circuit occurs. They are not necessary for the system to run
properly, but we always recommend using fuses or circuit breakers for safety
purposes. There are three different locations that we recommend installing
fuses or breakers: first, between the charge controller and battery bank,
second, between the charge controller and solar panels, and third would be between
the battery bank and inverter.

To
determine the fuse size needed between the charge controller and battery bank you
simply match the amperage rating on the charge controller. For instance, if you
have one of our 40Amp charge controllers, we would recommend using an 40Amp
fuse.

The
second fuse between your solar panels and charge controller is a little bit
different to figure out. The size of this fuse is dependent on how many solar
panels you have and how they are connected (series, parallel, or
series/parallel). If the panels are connected in series, the voltage of each
panel is added but the amperage stays the same. For example, if you have four
100W panels connected in series, each producing 20 volts and 5 amps, the total
output would be 80 volts and 5 amps. We then take the total amperage and
multiply it by a safety factor of 25% (5A x 1.25) giving us the fuse rating of
6.25A or 10A if we round up. If you have a parallel connection, where the
amperage of the panels is added up but the voltage stays the same, you would
have to add up the amperage of each panel and then we add a 25% industry rule
to figure out the fuse size. For example, if you had four 100W panels hooked in
a parallel connection, each panel produces about 5 Amps, so we would use this
equation (4 * 5 * 1.25) = 28.75 Amps, so in this instance we would recommend a
30 Amp fuse.

The
last fuse that we recommend in the system would be if you are using an
inverter. This fuse would be between your inverter and the battery bank. The
fuse size is usually stated in the manual and most inverters already have built
in fuses/breakers. The rule of thumb that we use here would be “Continuous
Watts / Battery Voltage times 1.25, for example a typical 1000W 12V inverter
draws up around 83 continuous amps and we would add the 25% safety factor which
comes out to 105 Amps, so we would recommend a 150A fuse.

This
is a brief introduction and summary for fusing your system. There are other
aspects such as cable size/length and fuse/breaker types that are important. We
recommend giving us a call for more information!


We will be happy to hear your thoughts

      Leave a reply

      Rubattery
      Logo